SPECIFICATIONS FOR PTFE LINED PIPE, FITTINGS AND VALVES

 
     

This specification covers factory made PTFE lined metal pipe, fittings & valve primarily intended for conveying corrosive fluids.

All the technical specifications of our PTFE / PFA / FEP lined piping systemS generally exceeds the relevant ASTM F 1545-95 Standard specifications. This specification covers ANSI 150# PTFE lined pipe & fittings in nominal diameter from 25NB to 300NB.

Marerial of Construction: CS PTFE / PFA / FEP lined

Pipe & Fittings material : ASTM A106 Gr.B, in compliance with ANSI B 36.10. According to schedule 40 from 25NB to 150NB, schedule 30 from 200NB to 250NB & schedule 20 for 300NB.

Flange material: IS 2062 Gr.B ANSI B 16.5, ASA 150# for drilled holes

Valve body material: WCB casting as per lS-1 030

SS304 casting as per ASTM A351 gradeCF8

SS316 casting as per ASTM A351 gradeCF8M

PTFE liner for pipes: Isostatically molded liner with even pressure throughout the length, molded from standard resin as per ASTM D 1457, white color.

Lined fittings: Fittings are insitu molded in PTFE by isostatic molding process molded from standard resin as per ASTM D1457.

Lined Valves: Valves are lined with PTFE / PFA / FEP

Lining material- Resin Type

Standard Resin Specification Standar LinerColor

PTFE Polytetrafluoroethylene ASTMD1457 White

PFA Perfluoro [Alkoxyalkane] copolymer ASTM D 3307 Natural

FEP Perfluoro [Ethylene-Propylene] copolymer ASTM D 2116 Green

Lining Thickness: 3 to 8 mm from 25NB upto 300NB depends on size & location

Standard for Pipe: Collared ends with backing flange as per ANSI B16.5 ASA 150#, one end loose flange and other end fixed flange.

Standard for fittings: All fittings are with fixed welded flanges, loose flanges can be offered on extra cost.

Vents holes: Each pipe having two vent holes that will release any pressure between the liner and the housings.

Tolerance for pipe lingth : + 3.2 mm

Tolerance for flange bolt hole : + 1.6 mm

Inspection and testing : Pipes and fittings are tested with a non destructive high voltage tester at an output voltage of 10KV and hydrostatic pressure test at 10 Kg/cm2, ball valves are tested at air pressure of 2Kg/cm 2

Pressure rating: Vacuume to 6 kg/cm 2

Temperature rating: - 29°C to 260°C

External finish : Pipes and fittings are paint externally by red oxide primer and valves are paint externally with two coats of paint

Bore size (ID), flare diameter and flange thickness:

Size

Lined pipe ID

Flare Diameter

Flange Thickness

NB

mm

As per ASTM F1545-95

without RF mm

25

18

47.6

14.5

40

32

68.3

14.5

50

42

87.3

16.5

80

67

117.5

18.5

100

88

150.8

18.5

150

138

203.2

23

200

186

255.6

23

250

234

311.2

25

300

282

365.1

33.6

 

Packing : Both ends of pipe are packed with good quality ply tightened with set of nut and bolts, fittings are packed with corrugated paper packing.